Abstract:

Aiming at the power grid fault for doubly fed induction generator(DIFG)of 2 MW,dynamic voltage restorer(DVR)based hybrid energy storage system composed of batteries and super-capacitors is presented to improve the fault penetration capacity of DIFG.The voltage level of DFIG stator is fully compensated during grid faults to keep the stator voltage,rotor current and DC side voltage in the normal levels.A simulation model of DFIG-DVR is established in Matlab/Simulink.The low voltage penetration during symmetrical and asymmetrical grid faults is simulated,and the high voltage penetration during symmetrical grid faults is also simulated.The simulation results indicate that the hybrid energy storage system based DVR can effectively improve the fault penetration capability of DFIG.

Basic Information:

DOI:10.20040/j.cnki.1000-7709.2016.07.048

China Classification Code:TM614

Citation Information:

[1]MENG Zhi-hong,REN Yong-feng,DU Peng-fei ,et al.Study on Fault Penetration Capacity of Doubly Fed Induction Generator Using Hybrid Energy Storage System Based on DVR[J].Water Resources and Power,2016,34(07):195-199.DOI:10.20040/j.cnki.1000-7709.2016.07.048.

Fund Information:

国家自然科学基金项目(51567020;51367012); 教育部新世纪优秀人才支持计划(NCET-11-1018); 内蒙古自治区自然科学基金项目(2015MS0532;2011BS0903); 内蒙古自治区“草原英才”工程(CYYC2013031); 风能太阳能利用技术省部共建教育部重点实验室开放基金项目(201403)

Published:  

2016-07-25

Publication Date:  

2016-07-25

quote

GB/T 7714-2015
MLA
APA
Search Advanced Search