nav emailalert searchbtn searchbox tablepage yinyongbenwen piczone journalimg journalInfo journalinfonormal searchdiv searchzone qikanlogo popupnotification paper paperNew
Abstract:

In order to study the measurement performance of ECT,taking the ECT of Roche coil as object,the influence of ambient temperature,adjacent phase current and harmonic factors on measurement accuracy was analyzed.The results show that the change of temperature can cause the ECT's fluctuating error to reach the half and above of 0.2Sbasic error's;the adjacent phase current affects the 0.2SECT's error but it has not over-error;Rogowski coil ECT can accurately measure the harmonic current,and has no influence on the measurement of fundamental wave current.The results provide theoretical basis for rational design of low-variable-ratio structure of ECT of Roche coil.

References

[1]罗苏南,田朝勃,赵希才.空心线圈电流互感器性能分析[J].中国电机工程学报,2004,24(3):108-113.

[2]王鹏,罗承沐,张贵新.基于低功率电流互感器的电子式电流互感器[J].电力系统自动化,2006,30(4):98-101.

[3]Fiber Optic Sensors Working Group.Optical Current Transducers for Power Systems:A Review[J].IEEE Trans.on Power Delivery,1994,9(4):1 778-1 788.

[4]Sanders G A,Blake J N,Rose A H,et.al.Commercialization of Fiber-optic Current and Voltage Sensors at Nxtphase[C]//The 15th Optical Fiber Sensors Conference Technical Digest.Portland,UK:OR,United States OFS,2002:31-34.

[5]周文中,赵国生,李海洋.Rogowski线圈测量误差分析及改进措施[J].电力系统保护与控制,2009,37(20):99-103.

[6]Bohnert K,Gabus P,Nehring J,et.al.Temperature and Vibration Insensitive Fiber-optic Current Sensor[J].Journal of Lightwave Technology,2002,20(2):267-276.

[7]Ramboz J D.Machinable Rogowski Coil Design and Calibration[J].IEEE Trans on Instrumentation and Measurement,1996,45(2):511-515.

[8]Blake J,Tantaswadi P,de Carvalho R T.In-line Sagnac Interferometer Current Sensor[J].IEEE Trans on Power Delivery,1996,11(1):116-121.

[9]孙卫明,潘峰,钟清,等.数字化电能计量技术[M].北京:中国电力出版社,2014.

[10]罗承沐,张贵新.电子式互感器与数字化变电站[M].北京:中国电力出版社,2012.

[11]GB/T 20840.8-2007,互感器第8部分:电子式电流互感器[S].北京:中国标准出版社,2007.

Basic Information:

DOI:10.20040/j.cnki.1000-7709.2017.03.047

China Classification Code:TM452

Citation Information:

[1]HU Hao-liang,PU Yan,XIONG Qian-zhu ,et al.Test and Analysis of Low Ratio ECT Performance Measurement[J].Water Resources and Power,2017,35(03):186-189.DOI:10.20040/j.cnki.1000-7709.2017.03.047.

Fund Information:

国家电网公司科技项目(JL71-15-040)

Published:  

2017-03-25

Publication Date:  

2017-03-25